Power Transformers

← All product families

01 / 08

Power Transformers

For transmission, generation and large industrial connections where electrical duty, site conditions and test evidence must be aligned before production.

Large oil-immersed power transformer

APPLICATION

Specified for the work it needs to do.

Large power transformers are specified around the network they serve. WEYPLEX coordinates the incoming data sheet with a suitable manufacturer, then confirms the proposed design and documentation for that model.

Common applications

  • Utility transmission and substations
  • Power generation connections
  • Large industrial power systems
  • Data center substations

PRODUCT CAPABILITIES

Power transformer voltage classes

Our manufacturing partners offer power transformer families in 35 kV, 110 kV, 220 kV, 330 kV and 500 kV classes. We confirm the ratings and applicable certifications for the quoted model.

35–500 kVFive power transformer voltage classes
Project-specificMVA, cooling, tap range, losses and sound levels to be checked for the quoted design
Model documentationModel data sheet, loss calculation, routine/type test reports and any required short-circuit evidence

EU large-transformer efficiency is assessed using the applicable Peak Efficiency Index; U.S. requirements depend on equipment scope and project specifications. We verify the applicable efficiency requirements for the quoted model.

MANUFACTURER CATALOGUE TABLES

Power transformer catalogue ratings

Compare representative 22-series loss values across the five voltage classes. Final values depend on the selected design.

35 kV · 22 series · three-phase, double-winding15 ratings · click to view

One published configuration from the manufacturer's voltage-class document. No-load and load losses are expressed in kW. Other winding, tapping and voltage combinations have separate values in the original file and require a project-specific data sheet.

Rated capacity kVANo-load loss kWLoad loss kWNo-load current %Impedance %
31501.720.70.457.0
40002.024.60.457.0
50002.428.20.457.0
63002.931.50.458.0
80004.034.60.358.0
100004.840.80.358.0
125005.548.40.308.0
160006.759.20.308.0
200007.971.60.308.0
250009.484.60.2510.0
3150011.1100.80.2510.0
4000012.6122.50.2012~15
5000014.8145.10.2012~15
6300017.1175.70.2012~15
7500019.3229.70.2012~15
110 kV · 22 series · three-phase, double-winding16 ratings · click to view

One published configuration from the manufacturer's voltage-class document. No-load and load losses are expressed in kW. Other winding, tapping and voltage combinations have separate values in the original file and require a project-specific data sheet.

Rated capacity kVANo-load loss kWLoad loss kWNo-load current %Impedance %
63004.1320.310.5
80004.9380.310.5
100005.8450.310.5
125006.8530.310.5
160008.365.70.310.5
200009.7790.310.5
2500011.4940.2510.5
3150013.51110.2510.5
4000016.21330.2510.5
5000019.41580.2510.5
6300022.91870.210.5
7500026.02120.212~14
9000029.92450.212~14
12000037.33030.212~14
15000044.13590.1812~14
18000049.54110.1812~14
220 kV · 22 series · three-phase, double-winding16 ratings · click to view

One published configuration from the manufacturer's voltage-class document. No-load and load losses are expressed in kW. Other winding, tapping and voltage combinations have separate values in the original file and require a project-specific data sheet.

Rated capacity kVANo-load loss kWLoad loss kWNo-load current %Impedance %
31500151150.312~14
40000181340.312~14
50000211610.312~14
63000251880.312~14
75000292130.312~14
90000342460.312~14
120000413040.2512~14
150000493600.2512~14
160000513780.2512~14
180000564130.2512~14
240000704840.212~14
300000835770.212~14
360000956620.212~14
370000976750.212~14
4000001037160.1812~14
4200001067420.1812~14
330 kV · 22 series · three-phase, double-winding9 ratings · click to view

One published configuration from the manufacturer's voltage-class document. No-load and load losses are expressed in kW. Other winding, tapping and voltage combinations have separate values in the original file and require a project-specific data sheet.

Rated capacity kVANo-load loss kWLoad loss kWNo-load current %Impedance %
90000372470.2814~15
120000473060.2814~15
150000563620.2614~15
180000644150.2414~15
240000805150.2214~15
3600001097220.2214~15
3700001117360.1914~15
4000001187800.1914~15
72000018312120.2514~15
500 kV · 22 series · three-phase, double-winding15 ratings · click to view

One published configuration from the manufacturer's voltage-class document. No-load and load losses are expressed in kW. Other winding, tapping and voltage combinations have separate values in the original file and require a project-specific data sheet.

Rated capacity kVANo-load loss kWLoad loss kWNo-load current %Impedance %
120000413560.1314
160000504410.1314
240000695990.114
300000807070.114
370000948100.0814
400000968550.0814
4200001028600.0814或16
4800001109540.0814或16
60000014312020.0814或16
72000016813820.0814或16
75000017314220.0816或18
78000017614670.0816或18
86000019015750.0816或18
114000023719490.0816或18
117000024219800.0816或18

Manufacturer catalogue values are not a guarantee for a quoted transformer. Model-specific winding, tap, cooling, rated voltage, losses, impedance and test reports must be confirmed. EU large-transformer efficiency assessment requires the applicable peak efficiency index; we review the applicable efficiency requirements for the quoted model.

PROJECT INQUIRY

What helps us review your requirement.

A data sheet or single-line diagram is the best starting point. If some information is missing, send what you have.

Network duty
Rated power, voltage ratio, frequency and system fault level
Operating conditions
Cooling method, ambient conditions, altitude and installation layout
Performance targets
Losses, impedance, sound limits and insulation levels
Project evidence
Applicable standards, required tests, inspection points and delivery schedule

Documentation follows the proposed model.

Standards, certificates and test reports vary by manufacturer and configuration. The quotation will identify the proposed manufacturer, applicable documents, inspection scope and agreed delivery terms.

How we review quality and documentation →

Ready to discuss your project?

Share your electrical requirements and target schedule with the WEYPLEX project desk.

Get a Project Quote