03 / 08
Dry-Type Transformers
For indoor electrical distribution where enclosure, ventilation, sound and fire-safety requirements shape the installation.

APPLICATION
Specified for the work it needs to do.
Dry-type transformer selection depends on the building and load as much as the rating. We coordinate technical requirements with the proposed manufacturing partner and confirm the requested model documentation.
Common applications
- Data centers and critical facilities
- Commercial buildings
- Industrial plants and infrastructure
PRODUCT CAPABILITIES
Dry-type families in the archive.
Our manufacturing partners offer resin-insulated SC(B)12, SC(B)14 and SC(B)18 6/10 kV families from 30 to 2,500 kVA; a 20 kV SC(B)12/18 family from 50 to 2,500 kVA; and a 35/0.4 kV SC(B)10 family from 50 to 2,500 kVA. The range also includes an SCZ(B)10 on-load tap-changing family.
Compare model-specific loss values in the tables below. A current signed data sheet and test report are still needed before making a model-specific EU or U.S. efficiency claim.
MANUFACTURER CATALOGUE TABLES
Dry-type transformer technical data
Catalogue rows cover 6/10 kV resin-insulated and amorphous-core series, plus 20 kV dry-type series. Expand a series to compare capacity, losses, impedance and acoustic figures.
SC(B)18 6kV, 10kV18 ratings · click to view
Catalogue loss figures are shown as published at the stated 75 °C reference. HV voltage options, tapping arrangement and vector group vary by model; confirm these in the quoted data sheet.
| kVA | No-load loss W | Load loss W at 75 °C | Impedance % | Sound pressure dB(A) |
|---|---|---|---|---|
| 30 | 105 | 555 | 4 | 44 |
| 50 | 155 | 785 | 4 | 44 |
| 80 | 210 | 1080 | 4 | 45 |
| 100 | 230 | 1235 | 4 | 45 |
| 125 | 270 | 1450 | 4 | 46 |
| 160 | 310 | 1670 | 4 | 46 |
| 200 | 360 | 1990 | 4 | 47 |
| 250 | 415 | 2170 | 4 | 47 |
| 315 | 510 | 2735 | 4 | 48 |
| 400 | 570 | 3140 | 4 | 48 |
| 500 | 670 | 3835 | 4 | 49 |
| 630 | 750 | 4695 | 6 | 50 |
| 800 | 875 | 5475 | 6 | 51 |
| 1000 | 1020 | 6430 | 6 | 52 |
| 1250 | 1205 | 7610 | 6 | 53 |
| 1600 | 1415 | 9230 | 6 | 53 |
| 2000 | 1760 | 11420 | 6 | 54 |
| 2500 | 2080 | 13540 | 6 | 54 |
SC(B)14 6kV, 10kV18 ratings · click to view
Catalogue loss figures are shown as published at the stated 75 °C reference. HV voltage options, tapping arrangement and vector group vary by model; confirm these in the quoted data sheet.
| kVA | No-load loss W | Load loss W at 75 °C | Impedance % | Sound pressure dB(A) |
|---|---|---|---|---|
| 30 | 130 | 555 | 4 | 44 |
| 50 | 185 | 785 | 4 | 44 |
| 80 | 250 | 1080 | 4 | 45 |
| 100 | 270 | 1235 | 4 | 45 |
| 125 | 320 | 1450 | 4 | 46 |
| 160 | 365 | 1670 | 4 | 46 |
| 200 | 420 | 1990 | 4 | 47 |
| 250 | 490 | 2170 | 4 | 47 |
| 315 | 600 | 2735 | 4 | 48 |
| 400 | 665 | 3140 | 4 | 48 |
| 500 | 790 | 3835 | 4 | 49 |
| 630 | 885 | 4695 | 6 | 50 |
| 800 | 1035 | 5475 | 6 | 51 |
| 1000 | 1200 | 6430 | 6 | 52 |
| 1250 | 1420 | 7610 | 6 | 53 |
| 1600 | 1665 | 9230 | 6 | 53 |
| 2000 | 2075 | 11420 | 6 | 54 |
| 2500 | 2450 | 13540 | 6 | 54 |
SC(B)12 6kV, 10kV18 ratings · click to view
Catalogue loss figures are shown as published at the stated 75 °C reference. HV voltage options, tapping arrangement and vector group vary by model; confirm these in the quoted data sheet.
| kVA | No-load loss W | Load loss W at 75 °C | Impedance % | Sound pressure dB(A) |
|---|---|---|---|---|
| 30 | 150 | 620 | 4 | 44 |
| 50 | 215 | 870 | 4 | 44 |
| 80 | 295 | 1200 | 4 | 45 |
| 100 | 320 | 1370 | 4 | 45 |
| 125 | 375 | 1610 | 4 | 46 |
| 160 | 430 | 1860 | 4 | 46 |
| 200 | 495 | 2200 | 4 | 47 |
| 250 | 575 | 2410 | 4 | 47 |
| 315 | 705 | 3030 | 4 | 48 |
| 400 | 785 | 3480 | 4 | 48 |
| 500 | 930 | 4260 | 4 | 49 |
| 630 | 1040 | 5200 | 6 | 50 |
| 800 | 1215 | 6070 | 6 | 51 |
| 1000 | 1415 | 7090 | 6 | 52 |
| 1250 | 1670 | 8460 | 6 | 53 |
| 1600 | 1960 | 10240 | 6 | 53 |
| 2000 | 2440 | 12610 | 6 | 54 |
| 2500 | 2880 | 14990 | 6 | 54 |
SCZ(B)10 6kV, 10kV13 ratings · click to view
Catalogue loss figures are shown as published at the stated 75 °C reference. HV voltage options, tapping arrangement and vector group vary by model; confirm these in the quoted data sheet.
| kVA | No-load loss W | Load loss W at 75 °C | Impedance % | Sound pressure dB(A) |
|---|---|---|---|---|
| 200 | 640 | 2250 | 4 | 47 |
| 250 | 735 | 2450 | 4 | 47 |
| 315 | 990 | 3150 | 4 | 48 |
| 400 | 1120 | 3730 | 4 | 48 |
| 500 | 1290 | 4560 | 4 | 49 |
| 630 | 1490 | 5390 | 4 | 50 |
| 630 | 1440 | 5550 | 6 | 50 |
| 800 | 1710 | 6550 | 6 | 51 |
| 1000 | 1980 | 7670 | 6 | 52 |
| 1250 | 2340 | 9080 | 6 | 53 |
| 1600 | 2720 | 10830 | 6 | 53 |
| 2000 | 3420 | 13280 | 6 | 54 |
| 2500 | 3960 | 15810 | 6 | 54 |
SC(B)10 35 0.4 kV17 ratings · click to view
Catalogue loss figures are shown as published at the stated 75 °C reference. HV voltage options, tapping arrangement and vector group vary by model; confirm these in the quoted data sheet.
| kVA | No-load loss W | Load loss W at 75 °C | Impedance % | Sound pressure dB(A) |
|---|---|---|---|---|
| 50 | 450 | 1240 | 6 | 50 |
| 80 | 600 | 1540 | 6 | 50 |
| 100 | 630 | 1820 | 6 | 51 |
| 125 | 670 | 2310 | 6 | 51 |
| 160 | 790 | 2450 | 6 | 51 |
| 200 | 880 | 2900 | 6 | 51 |
| 250 | 990 | 3320 | 6 | 51 |
| 315 | 1170 | 3940 | 6 | 51 |
| 400 | 1370 | 4720 | 6 | 51 |
| 500 | 1620 | 5810 | 6 | 52 |
| 630 | 1860 | 6720 | 6 | 52 |
| 800 | 2160 | 7970 | 6 | 52 |
| 1000 | 2430 | 9080 | 6 | 52 |
| 1250 | 2830 | 11090 | 6 | 53 |
| 1600 | 3240 | 13450 | 6 | 53 |
| 2000 | 3820 | 15900 | 6 | 54 |
| 2500 | 4450 | 19040 | 6 | 55 |
SCBH19 Amorphous Alloy Core13 ratings · click to view
Catalogue loss figures are shown as published at the stated 75 °C reference. HV voltage options, tapping arrangement and vector group vary by model; confirm these in the quoted data sheet.
| kVA | No-load loss W | Load loss W at 75 °C | Impedance % | Sound pressure dB(A) |
|---|---|---|---|---|
| 160 | 120 | 1670 | 4 | 53 |
| 200 | 140 | 1990 | 4 | 53 |
| 250 | 160 | 2170 | 4 | 53 |
| 315 | 195 | 2730 | 4 | 53 |
| 400 | 215 | 3140 | 4 | 53 |
| 500 | 250 | 3830 | 4 | 55 |
| 630 | 290 | 4690 | 6 | 55 |
| 800 | 335 | 5470 | 6 | 55 |
| 1000 | 385 | 6430 | 6 | 58 |
| 1250 | 455 | 7610 | 6 | 58 |
| 1600 | 530 | 9230 | 6 | 58 |
| 2000 | 700 | 11420 | 6 | 62 |
| 2500 | 840 | 13540 | 6 | 62 |
SCBH17 Amorphous Alloy Core13 ratings · click to view
Catalogue loss figures are shown as published at the stated 75 °C reference. HV voltage options, tapping arrangement and vector group vary by model; confirm these in the quoted data sheet.
| kVA | No-load loss W | Load loss W at 75 °C | Impedance % | Sound pressure dB(A) |
|---|---|---|---|---|
| 160 | 145 | 1670 | 4 | 53 |
| 200 | 170 | 1990 | 4 | 53 |
| 250 | 195 | 2170 | 4 | 53 |
| 315 | 235 | 2730 | 4 | 53 |
| 400 | 265 | 3140 | 4 | 53 |
| 500 | 305 | 3830 | 4 | 55 |
| 630 | 350 | 4690 | 6 | 55 |
| 800 | 410 | 5470 | 6 | 55 |
| 1000 | 470 | 6430 | 6 | 58 |
| 1250 | 550 | 7610 | 6 | 58 |
| 1600 | 645 | 9230 | 6 | 58 |
| 2000 | 850 | 11420 | 6 | 62 |
| 2500 | 1020 | 13540 | 6 | 62 |
SCBH15 Amorphous Alloy Core13 ratings · click to view
Catalogue loss figures are shown as published at the stated 75 °C reference. HV voltage options, tapping arrangement and vector group vary by model; confirm these in the quoted data sheet.
| kVA | No-load loss W | Load loss W at 75 °C | Impedance % | Sound pressure dB(A) |
|---|---|---|---|---|
| 160 | 170 | 1850 | 4 | 53 |
| 200 | 200 | 2210 | 4 | 53 |
| 250 | 230 | 2410 | 4 | 53 |
| 315 | 280 | 3040 | 4 | 53 |
| 400 | 310 | 2490 | 4 | 53 |
| 500 | 360 | 4260 | 4 | 55 |
| 630 | 410 | 5220 | 6 | 55 |
| 800 | 480 | 6080 | 6 | 55 |
| 1000 | 550 | 7140 | 6 | 58 |
| 1250 | 650 | 8460 | 6 | 58 |
| 1600 | 760 | 10260 | 6 | 58 |
| 2000 | 1000 | 12690 | 6 | 62 |
| 2500 | 1200 | 15040 | 6 | 62 |
SC(B)18 · 20 kV15 ratings · click to view
20/0.4 kV; Dyn11 for this series. Load loss is given at 120 °C for insulation class F and 145 °C for class H.
| kVA | No-load loss W | Load loss W · F | Load loss W · H | Impedance % |
|---|---|---|---|---|
| 50 | 235 | 1110 | 1180 | 6 |
| 100 | 375 | 1790 | 1920 | 6 |
| 160 | 460 | 2220 | 2380 | 6 |
| 200 | 500 | 2650 | 2830 | 6 |
| 250 | 570 | 3080 | 3290 | 6 |
| 315 | 660 | 3670 | 3920 | 6 |
| 400 | 785 | 4360 | 4660 | 6 |
| 500 | 920 | 5210 | 5570 | 6 |
| 630 | 1045 | 6160 | 6590 | 6 |
| 800 | 1200 | 7430 | 7960 | 6 |
| 1000 | 1420 | 8800 | 9360 | 6 |
| 1250 | 1625 | 10400 | 11100 | 6 |
| 1600 | 1910 | 12400 | 13300 | 6 |
| 2000 | 2215 | 14700 | 15800 | 6 |
| 2500 | 2650 | 17400 | 18600 | 6 |
SC(B)14 · 20 kV15 ratings · click to view
20/0.4 kV; Dyn11 for this series. Load loss is given at 120 °C for insulation class F and 145 °C for class H.
| kVA | No-load loss W | Load loss W · F | Load loss W · H | Impedance % |
|---|---|---|---|---|
| 50 | 260 | 1110 | 1180 | 6 |
| 100 | 415 | 1790 | 1920 | 6 |
| 160 | 510 | 2220 | 2380 | 6 |
| 200 | 555 | 2650 | 2830 | 6 |
| 250 | 635 | 3080 | 3290 | 6 |
| 315 | 735 | 3670 | 3920 | 6 |
| 400 | 875 | 4360 | 4660 | 6 |
| 500 | 1025 | 5210 | 5570 | 6 |
| 630 | 1160 | 6160 | 6590 | 6 |
| 800 | 1330 | 7430 | 7960 | 6 |
| 1000 | 1575 | 8800 | 9360 | 6 |
| 1250 | 1805 | 10400 | 11100 | 6 |
| 1600 | 2120 | 12400 | 13300 | 6 |
| 2000 | 2460 | 14700 | 15800 | 6 |
| 2500 | 2945 | 17400 | 18600 | 6 |
SC(B)12 · 20 kV15 ratings · click to view
20/0.4 kV; Dyn11 for this series. Load loss is given at 120 °C for insulation class F and 145 °C for class H.
| kVA | No-load loss W | Load loss W · F | Load loss W · H | Impedance % |
|---|---|---|---|---|
| 50 | 275 | 1230 | 1310 | 6 |
| 100 | 435 | 1990 | 2130 | 6 |
| 160 | 535 | 2470 | 2640 | 6 |
| 200 | 585 | 2940 | 3140 | 6 |
| 250 | 670 | 3420 | 3660 | 6 |
| 315 | 775 | 4080 | 4360 | 6 |
| 400 | 920 | 4840 | 5180 | 6 |
| 500 | 1080 | 5790 | 6190 | 6 |
| 630 | 1220 | 6840 | 7320 | 6 |
| 800 | 1400 | 8260 | 8840 | 6 |
| 1000 | 1660 | 9780 | 10400 | 6 |
| 1250 | 1900 | 11500 | 12300 | 6 |
| 1600 | 2230 | 13800 | 14800 | 6 |
| 2000 | 2590 | 16300 | 17500 | 6 |
| 2500 | 3100 | 19300 | 20700 | 6 |
The 35/10 kV sheet is excluded pending confirmation of inconsistent loss units in its header and values. These are legacy manufacturer tables, not current signed model data sheets. EU Tier 2 or U.S. DOE efficiency status cannot be inferred from the tables alone; confirm voltage, frequency, temperature reference and test basis for the actual quote.
PROJECT INQUIRY
What helps us review your requirement.
A data sheet or single-line diagram is the best starting point. If some information is missing, send what you have.
- Load profile
- Capacity, voltage, frequency and expected load variation
- Installation
- Enclosure, clearances, ventilation and ambient temperature
- Performance
- Losses, impedance, sound limits and insulation class
- Project evidence
- Applicable IEC or IEEE specification and requested test reports
Documentation follows the proposed model.
Standards, certificates and test reports vary by manufacturer and configuration. The quotation will identify the proposed manufacturer, applicable documents, inspection scope and agreed delivery terms.
How we review quality and documentation →Ready to discuss your project?
Share your electrical requirements and target schedule with the WEYPLEX project desk.