Distribution Transformers

← All product families

02 / 08

Distribution Transformers

For utility, commercial and industrial distribution networks that need the right capacity, efficiency and site configuration.

Oil-immersed distribution transformer with cooling fins

APPLICATION

Specified for the work it needs to do.

A distribution transformer must suit the network and its operating pattern. We review the specification, efficiency target and local utility requirements before identifying an appropriate production option.

Common applications

  • Utility distribution networks
  • Industrial facilities
  • Commercial power distribution

PRODUCT CAPABILITIES

Published 10 kV distribution families.

Our manufacturing partners offer oil-immersed S13-M, S20-M and S22-M sealed units; S13-M·RL, S20-M·RL and S22-M·RL three-dimensional wound-core units; and SH/SBH15-M, SH/SBH21-M and SH/SBH25-M amorphous-core variants.

EU Ecodesign scope and Tier 2 →

MANUFACTURER CATALOGUE TABLES

10 kV distribution transformer technical data

Compare the 10 kV distribution transformer models below. The tables preserve catalogue losses and show how ratings vary by series.

S13-M · Oil-immersed, fully sealed19 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
S13-M-30/103080630/6001.24
S13-M-50/1050100910/8701.044
S13-M-63/10631101090/10400.964
S13-M-80/10801301310/12500.964
S13-M-100/101001501580/15000.884
S13-M-125/101251701890/18000.884
S13-M-160/101602002310/22000.84
S13-M-200/102002402730/26000.84
S13-M-250/102502903200/30500.724
S13-M-315/103153403830/36500.724
S13-M-400/104004104520/43000.644
S13-M-500/105004805410/51500.644
S13-M-630/1063057062000.484.5
S13-M-800/1080070075000.484.5
S13-M-1000/101000830103000.484.5
S13-M-1250/101250970120000.44.5
S13-M-1600/1016001170145000.44.5
S13-M-2000/1020001360183000.325
S13-M-2500/1025001600212000.325
S20-M · Oil-immersed, fully sealed19 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
S20-M-30/103070505/4801.24
S20-M-50/105090730/6951.044
S20-M-63/1063100870/8300.964
S20-M-80/10801151050/10000.964
S20-M-100/101001351265/12000.884
S20-M-125/101251501510/14400.884
S20-M-160/101601801850/17600.84
S20-M-200/102002152185/20800.84
S20-M-250/102502602560/24400.724
S20-M-315/103153053065/29200.724
S20-M-400/104003703615/34400.644
S20-M-500/105004304330/41200.644
S20-M-630/1063051049600.484.5
S20-M-800/1080063060000.484.5
S20-M-1000/10100074582400.484.5
S20-M-1250/10125087096000.44.5
S20-M-1600/1016001050116000.44.5
S20-M-2000/1020001225146400.325
S20-M-2500/1025001440169600.325
S22-M · Oil-immersed, fully sealed19 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
S22-M-30/103065455/4301.24
S22-M-50/105080655/6251.044
S22-M-63/106390785/7450.964
S22-M-80/1080105945/9000.964
S22-M-100/101001201140/10800.884
S22-M-125/101251351360/12950.884
S22-M-160/101601601665/15850.84
S22-M-200/102001901970/18700.84
S22-M-250/102502302300/21950.724
S22-M-315/103152702760/26300.724
S22-M-400/104003303250/30950.644
S22-M-500/105003853900/37100.644
S22-M-630/1063046044600.484.5
S22-M-800/1080056054000.484.5
S22-M-1000/10100066574150.484.5
S22-M-1250/10125078086400.44.5
S22-M-1600/101600940104400.44.5
S22-M-2000/1020001085131800.325
S22-M-2500/1025001280152700.325
S13-M·RL · Three-dimensional wound core19 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
S13-M·RL-30/103080630/6001.24
S13-M·RL-50/1050100910/8701.044
S13-M·RL-63/10631101090/10400.964
S13-M·RL-80/10801301310/12500.964
S13-M·RL-100/101001501580/15000.884
S13-M·RL-125/101251701890/18000.884
S13-M·RL-160/101602002310/22000.84
S13-M·RL-200/102002402730/26000.84
S13-M·RL-250/102502903200/30500.724
S13-M·RL-315/103153403830/36500.724
S13-M·RL-400/104004104520/43000.644
S13-M·RL-500/105004805410/51500.644
S13-M·RL-630/1063057062000.484.5
S13-M·RL-800/1080070075000.484.5
S13-M·RL-1000/101000830103000.484.5
S13-M·RL-1250/101250970120000.44.5
S13-M·RL-1600/1016001170145000.44.5
S13-M·RL-2000/1020001360183000.325
S13-M·RL-2500/1025001600212000.325
S20-M·RL · Three-dimensional wound core19 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
S20-M·RL-30/103070505/4801.24
S20-M·RL-50/105090730/6951.044
S20-M·RL-63/1063100870/8300.964
S20-M·RL-80/10801151050/10000.964
S20-M·RL-100/101001351265/12000.884
S20-M·RL-125/101251501510/14400.884
S20-M·RL-160/101601801850/17600.84
S20-M·RL-200/102002152185/20800.84
S20-M·RL-250/102502602560/24400.724
S20-M·RL-315/103153053065/29200.724
S20-M·RL-400/104003703615/34400.644
S20-M·RL-500/105004304330/41200.644
S20-M·RL-630/1063051049600.484.5
S20-M·RL-800/1080063060000.484.5
S20-M·RL-1000/10100074582400.484.5
S20-M·RL-1250/10125087096000.44.5
S20-M·RL-1600/1016001050116000.44.5
S20-M·RL-2000/1020001225146400.325
S20-M·RL-2500/1025001440169600.325
S22-M·RL · Three-dimensional wound core19 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
S22-M·RL-30/103065455/4301.24
S22-M·RL-50/105080655/6251.044
S22-M·RL-63/106390785/7450.964
S22-M·RL-80/1080105945/9000.964
S22-M·RL-100/101001201140/10800.884
S22-M·RL-125/101251351360/12950.884
S22-M·RL-160/101601601665/15850.84
S22-M·RL-200/102001901970/18700.84
S22-M·RL-250/102502302300/21950.724
S22-M·RL-315/103152702760/26300.724
S22-M·RL-400/104003303250/30950.644
S22-M·RL-500/105003853900/37100.644
S22-M·RL-630/1063046044600.484.5
S22-M·RL-800/1080056054000.484.5
S22-M·RL-1000/10100066574150.484.5
S22-M·RL-1250/10125078086400.44.5
S22-M·RL-1600/101600940104400.44.5
S22-M·RL-2000/1020001085131800.325
S22-M·RL-2500/1025001280152700.325
SH15-M · Amorphous alloy core4 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
SH15-M-303033630/6001.54
SH15-M-505043910/8701.24
SH15-M-6363501090/10401.14
SH15-M-8080601310/125014
SBH15-M · Amorphous alloy core15 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
SBH15-M-100100751580/15000.9—
SBH15-M-125125851890/18000.8—
SBH15-M-1601601002310/22000.6—
SBH15-M-2002001202730/26000.6—
SBH15-M-2502501403200/30500.6—
SBH15-M-3153151703830/36500.5—
SBH15-M-4004002004520/43000.5—
SBH15-M-5005002405410/51500.5—
SBH15-M-63063032062000.34.5
SBH15-M-80080038075000.34.5
SBH15-M-10001000450103000.34.5
SBH15-M-12501250530120000.24.5
SBH15-M-16001600630145000.24.5
SBH15-M-20002000720183000.25.5
SBH15-M-25002500865212000.25.5
SH21-M · Amorphous alloy core4 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
SH21-M-303033535/5101.54
SH21-M-505043780/7451.24
SH21-M-636350930/8901.14
SH21-M-8080601120/107014
SBH21-M · Amorphous alloy core15 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
SBH21-M-100100751350/12850.9—
SBH21-M-125125851615/15400.8—
SBH21-M-1601601001975/18800.6—
SBH21-M-2002001202330/22250.6—
SBH21-M-2502501402735/26100.6—
SBH21-M-3153151703275/31200.5—
SBH21-M-4004002003865/36750.5—
SBH21-M-5005002404625/44000.5—
SBH21-M-63063032053000.34.5
SBH21-M-80080038064150.34.5
SBH21-M-1000100045088000.34.5
SBH21-M-12501250530102600.24.5
SBH21-M-16001600630124000.24.5
SBH21-M-20002000710148000.25
SBH21-M-25002500860171500.25
SH25-M · Amorphous alloy core4 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
SH25-M-303025510/4801.54
SH25-M-505035735/7001.24
SH25-M-636340880/8401.14
SH25-M-8080501060/101014
SBH25-M · Amorphous alloy core15 ratings · click to view

Primary voltage options in the source: 6, 6.3, 10, 10.5 and 11 kV; secondary: 0.4 kV. For ratings up to 500 kVA, load-loss values separated by a slash are published as Dyn11 / Yyn0. Confirm the applicable value for the quoted vector group.

ModelkVANo-load loss WLoad loss WNo-load current %Impedance %
SBH25-M-100100601270/12150.9—
SBH25-M-125125701530/14500.8—
SBH25-M-160160801870/17800.6—
SBH25-M-200200952210/21000.6—
SBH25-M-2502501102590/24700.6—
SBH25-M-3153151353100/29500.5—
SBH25-M-4004001603660/34800.5—
SBH25-M-5005001904380/41700.5—
SBH25-M-63063025050200.34.5
SBH25-M-80080030060750.34.5
SBH25-M-1000100036083400.34.5
SBH25-M-1250125042597200.24.5
SBH25-M-16001600500117450.24.5
SBH25-M-20002000550140000.25
SBH25-M-25002500670162300.25

The manufacturer confirms final loss values for the selected model. EU or U.S. compliance must be established from the applicable configuration, frequency, test method and current signed data sheet.

PROJECT INQUIRY

What helps us review your requirement.

A data sheet or single-line diagram is the best starting point. If some information is missing, send what you have.

Electrical ratings
Capacity, primary and secondary voltage, phase and frequency
Installation
Indoor or outdoor location, footprint and environmental conditions
Efficiency
Loss limits and applicable local efficiency rules
Project evidence
Utility specification, required approvals, tests and delivery date

Documentation follows the proposed model.

Standards, certificates and test reports vary by manufacturer and configuration. The quotation will identify the proposed manufacturer, applicable documents, inspection scope and agreed delivery terms.

How we review quality and documentation →

Ready to discuss your project?

Share your electrical requirements and target schedule with the WEYPLEX project desk.

Get a Project Quote